High Efficiency

Singapore is a secure regional data center hub with a stable government, a modern infrastructure, and global connectivity. Taking full advantage of this, the client in this case study leverages its market-leading presence and experience operating some of the most modern data centers in the world to offer class-leading telecommunications, cloud-based applications, and data services. Strategically located in the western part of Singapore, their new mission-critical facility is designed to meet the increased security and reliability demands of the next generation of power-intensive IT deployments.

Informação de projetos

UPS type: Dynamic UPS
Power module: 2,500 kVA
UPS rating: 2,000 kW@ 0.8PF of net usable power
Engine rating: Standby rated at 2,500 kVa
Phase 1 install: 8 modules
Total capacity: 16 MW
Operating voltage: 400V / 50Hz
Configuration: Tier III, Concurrently maintainable
Install: Indoor

Downloads

  • Client case: High Efficiency

Estádio

Desafio do Projeto

The new data center joined a network of eight existing data centers in Singapore. Its geographical separation, coupled with the company’s internal fiber optic network, ideally positioned the site for disaster recovery and business continuity services. Operational efficiency was of primary importance to the engineering team. Within the UPS market there are conflicting messages about the efficiency of static and dynamic UPS systems: vendors of Project challenge both technologies were touting efficiencies in the high 90’s at 100% load.

After extensive discussions with both static and dynamic UPS system providers, it was apparent that while static UPS systems initially seemed more efficient, many of the potential operational losses were removed from their calculations, i.e. air-conditioning, battery charging, and connection losses. The client also identified additional equipment needed to offer a comparable level of harmonic filtration to that of dynamic systems.

Solução de projeto

After a detailed study to assess the true total cost of ownership, the client opted for the solution with the lowest operational cost: dynamic UPS equipment from HITEC Power Protection. The analysis pointed to several hidden costs for static UPS. First, high efficiencies come when the unit is operating in a near-bypass mode that provides very little power conditioning. Next, the Static UPS system could only be installed in a dust free, air-conditioned environment to protect the power electronics.

Also, the losses attributed to the increased number of connections, recharging and ventilation of the batteries tipped the scales. When these were factored back into the equation, the efficiency of the entire static UPS solution was actually more like 91%, versus the 97% on-line efficiency of the HITEC dynamic system.

It felt good for engineering to give back floor space for the business to use. we increased our billable footprint and at the same time demonstrated an efficient return on our power spends.

Casos de clientes

Confiança de mais de 500 clientes

Compreendendo o seu mercado, a HITEC fornece sempre as melhores soluções para cada projeto específico.

Conheça todos nossos casos de sucesso

Caso

Standard Data Center design with Continuous cooling by Dynamic UPS

Caso

Upgrading the prime minister’s office

Caso

Power protection for Bracell SP’s gas incineration system

Caso

Protection against historic weather events

Caso

Retrofit to PowerPRO2700 for data center